PQM Waveform Analyzer · v2 (proto)

New consolidated FPT report

Fill in the project metadata. You can upload captures and pick profiles on the next screen — nothing is required beyond the fields on this form to create a session.

Project
Rating & classification

Generator type drives the default block-load envelope AND the dynamic profile applied to the report:

  • critical → WmW dynamic ramp, ISO 8528-5 G4 (spec 019113.26.01-L1)
  • chiller → Chiller dynamic ramp, ISO 8528-5 G4 (spec 019113.26.01-L1)
  • HS → BMEP-driven load steps, ISO 8528-5 G3 (spec 019113.26.03-L1)
  • custom → CxA picks the dynamic profile and supplies load steps + pass/fail thresholds

The ISO 8528-5 class is derived automatically from the generator type (HS → G3, everything else → G4); that is why it is not asked here.

Nominal ratings

Rated kW anchors the load-percentage math (0/25/50/75/100 % of rated) and the dynamic-profile breakpoints per Amazon Rev G spec (IEC 2400 / 2800 kW, UL 2500 / 2750 kW).